FENIGAL-FG Water Technologies
Tel: +86-15052233707 [email protected] Industrial Water Systems · Membranes · EDI · Desalination
FENIGAL-FG Water Technologies Wuxi Fenigal · Industrial Water Division
Translate this website

Google Translate is loaded only when you open this panel, reducing unnecessary requests and layout work during the first page load.

Loading language options…
Request Quote

Product System

Professional Product Detail

Exclusive Offer Electrodeionization (EDI) : Advanced Solutions for Efficient Purification and Purification of Water

Enhanced Electrodeionization (EDI) for Industrial Applications: Purify, Optimize, and Boost ProductivityThe advantages of Electrodeionization (EDI) compared to Mixed Bed systems are numerous. EDI offers a more advanced technology, eliminating the need for regeneration chemicals or neutralization sys

Category: Product System
Exclusive Offer Electrodeionization (EDI) : Advanced Solutions for Efficient Purification and Purification of Water

Enhanced Electrodeionization (EDI) for Industrial Applications: Purify, Optimize, and Boost Productivity


The advantages of Electrodeionization (EDI) compared to Mixed Bed systems are numerous. EDI offers a more advanced technology, eliminating the need for regeneration chemicals or neutralization systems. This results in significantly lower operating costs and a more environmentally friendly solution. Additionally, EDI systems offer continuous and simplified operation, leading to improved process efficiency. Furthermore, with a smaller footprint and reduced building height requirement, EDI systems are easier to integrate into existing industrial facilities. Overall, EDI technology offers a cost-effective, environmentally friendly, and efficient alternative to Mixed Bed systems.


parameter data



Stack Name

MK-3PharmHT

MK-3MiniHT

Weight

Dimensions

Shipping weight (kg)

92

52

Dimensions
(cm as width x height x depth)

30 x 61 x 54

30 x 61 x 29

 

 

 

 

Feed Water Quality
Specifications

Total exchangeable anions (ppm as CaCO3)

< 25

< 25

Conductivity (μS/cm)

< 43

< 43

pH

4-11

4-11

Temperature (°C)

4.4-40

4.4-40

Hardness (ppm as CaCO3)

< 1.0

< 1.0

Silica (ppm as SiO2)

< 1.0

< 1.0

TOC (ppm)

< 0.5

< 0.5

Turbidity (NTU)

< 1.0

< 1.0

Color (APHA)

< 5

< 5

Chlorine (ppm)

< 0.05

< 0.05

Fe, Mn, H2S (ppm)

< 0.01

< 0.01

Oxidant

Not detected

Not detected

Oil and grease

Not detected

Not detected

SDI15

< 1.0

< 1.0

Product Water Quality

Resistivity (MOhm-cm)

> 10

> 10

TOC (ppb)

< 500

< 500

 

 

 

 

Operating Parameters

Maximum water production (m3/hr)

4.5

1.5

Minimum water production (m3/hr)

1.6

0.5

Typical designed water production (m3/hr)

2.0-4.5

0.5-1.5

Recovery

Up to 96%

Up to 93%

Voltage (VDC)

0-300

0-150

Amperage (ADC)

0-5.2

0-5.2

Inlet pressure (bar)

Counter-current: 4.1-6.9
Co-current: 3.1-6.9

Counter-current: 4.1-6.9
Co-current: 3.1-6.9

Dilute inlet/outlet standard pressure drop (bar)

1.4-2.8

1.4-2.8

Minimum pressure difference between dilute outlet and concentrate inlet (bar)

0.34

0.34

Number of 1 hour sanitization cycles

160

160

Maximum sanitization temperature (°C)

85

85


We'd like to send you EX Prices if you like them.

https://www.fgwater.com/Electro-deionisation-System/

Project Inquiry · Technical & Commercial

Send Your Water Treatment Requirement

Tell us the feedwater, required capacity, target water quality and project conditions. Your inquiry email will automatically include the page you are viewing so our team can understand the exact product, technology or reference that led to your request.

  • Feedwater source / available analysis
  • Design flow or required production capacity
  • Target product-water quality or process duty
  • Project country, operating conditions and delivery target
Inquiry context Current page details will be attached automatically.