FENIGAL-FG Water Technologies
Tel: +86-13646187144 [email protected] Industrial Water Systems · Membranes · EDI · Desalination
FENIGAL-FG Water Technologies Wuxi Fenigal · Industrial Water Division
Translate this website

Google Translate is loaded only when you open this panel, reducing unnecessary requests and layout work during the first page load.

Loading language options…
Request Quote

Ion Exchange and Adsorption Resin

Professional Product Detail

Strong Base Anion Resin for Condensate Polishing: A Selection Guide for Plant Chemists

Compare strong base anion resins for condensate polishing: Type I chemistry, gel versus macroporous matrices, chloride or hydroxide form, mixed bed pairing and operating limits.

Category: Ion Exchange and Adsorption Resin

Strong Base Anion Resin for Condensate Polishing: A Selection Guide for Plant Chemists

Condensate polishing is the last barrier between the steam cycle and the boiler or reactor circuit, and in a mixed bed the anion component usually sets the practical limit on run length. A strong base anion resin condensate polishing duty combines three things that work against each other: a very dilute feed where leakage appears almost immediately, a hot and oxygenated environment that attacks the organic matrix, and a requirement that the anion beads separate cleanly from the cation beads after every backwash. This guide sets out how to specify the anion component against published product data, where the boundaries of each grade lie, and which numbers to ask for before a purchase order is raised.

The values quoted below are taken from the manufacturers' published product data sheets. They are minimum or range values, not guarantees for a particular vessel, and the applicability of any grade must be confirmed against your own condensate chemistry and bed design.

What Condensate Polishing Asks of an Anion Resin

The ionic duties inside the polisher

In the hydrogen form of a mixed bed, the cation resin releases hydrogen ions and the anion resin takes up the corresponding anions. The anion component therefore has to remove chloride, sulfate, carbonate and bicarbonate, silica, and boron species, while also retaining the corrosion products that reach it in solution. Because the feed is essentially pure water, the ionic load is tiny, and the resin is judged on how low the leakage goes rather than on how much capacity it holds.

Why the anion component fails first

Three mechanisms dominate. First, the quaternary ammonium functional group degrades thermally and oxidatively, and the loss of strong base sites shows up as a rising anion leakage long before the bead physically disintegrates. Second, silica and boron are weakly held and are the first species to break through. Third, in a layered or mixed bed the anion resin is exposed to the incoming condensate first, so it also carries the load of any copper and iron corrosion products and any residual amines.

Controlling species and what they indicate

A rise in conductivity at the start of a run normally points to loss of strong base capacity. A late silica rise with normal conductivity points to weakly held anion breakthrough and is often a regeneration or flow-distribution issue rather than a capacity issue. Sodium in the condensate is generally a cation-side or corrosion-product signal, but it also indicates that the anion resin is not holding the ionic balance it was specified to hold.

The same observations can be read as a decision aid; the indications below summarise the diagnostic behaviour described above and add no new performance data.

Observation at the polisher

What it usually indicates

First thing to check

Conductivity rise early in the run

Loss of strong-base capacity (thermal and oxidative functional-group loss)

Anion-resin age; oxygen and temperature history

Late silica rise with normal conductivity

Weakly held anion breakthrough; a regeneration or flow-distribution issue

Regeneration efficiency and flow distribution

Sodium in the condensate

A cation-side or corrosion-product signal disturbing the ionic balance

Cation-bed condition and upstream corrosion products

Type I and Type II Strong Base Anion Resins

Functional group chemistry

Both types carry quaternary ammonium groups, and both are fully dissociated across the whole pH range encountered in condensate treatment. The difference is in the substituent on the nitrogen: Type I carries four alkyl groups, Type II carries one or more groups that include a hydrocarbon chain with a hydroxyl or ether functionality. Type I gives the strongest base character and the best performance on weakly ionised species such as silica and carbonic acid at the end of the exchange cycle.

Silica and boron behaviour

Silica removal is the practical discriminator. In condensate polishing and in final polishing duty after reverse osmosis, Type I resins hold their exchange capacity at the low ionic strength of the feed and give the lowest silica leakage. Type II resins release more silica and are generally reserved for bulk anion removal in industrial demineralisation, where regenerant economy matters more than final water quality.

Thermal and oxidative stability

Type II chemistry is the more temperature-sensitive of the two, and its usable window narrows further once the resin is converted to the hydroxide form. For condensate service, the grades listed in this guide are Type I materials, and the published temperature limits are quoted separately for the hydroxide and chloride forms because the hydroxide form is the more limiting.

Physical Structure: Gel, Macroporous and Uniform Particle Size

Gel matrix resins

Gel strong base anion resins such as AmberLite HPR550 OH are produced by polymerising a styrenic phase with a high proportion of crosslinking agent and give the highest exchange capacity per unit volume in condensate duty. Their structure is essentially non-porous when dry and becomes a continuous gel phase when wet. In clean condensate they deliver the lowest leakage and the longest service life. Their limitation is a lower tolerance of organic fouling and of sharp osmotic shock, which is why careful wet-out and controlled regeneration matter more with a gel than with a macroporous bead.

文章5 (3).jpg

Macroporous matrix resins

Macroporous strong base anion resins such as AmberLite HPR9000 OH and AmberLite HPR900 SO4 contain a permanent pore network formed by a porogen during polymerisation. The open structure tolerates organic material, physical stress and osmotic shock better, at the cost of a lower total exchange capacity per litre. They are the logical choice where the condensate carries corrosion products, where the bed sees frequent turnover, or where fouling rather than capacity is the limiting factor.

Uniform particle size and why the coefficient matters

The uniformity coefficient is the ratio of the sieve sizes passing 10 per cent and 40 per cent of the sample. A value of 1.10 or below means a genuinely narrow distribution; a value of 1.45 or above means a broad one. In a mixed bed this is not a cosmetic number. A narrow distribution gives a sharper interface between the cation and anion zones after backwash, lower pressure drop per unit bed depth, and more predictable kinetics. A broad distribution stratifies internally, which shows up as premature leakage and as a diffuse boundary that makes visual confirmation of layering unreliable.

Ionic Form at Delivery: Chloride or Hydroxide

Capacity figures are form-dependent

Total exchange capacity is always reported for a stated ionic form, and the same product can carry quite different numbers depending on that form. AmberLite HPR550 Cl is published at a minimum of 1.35 equivalents per litre in the chloride form, while AmberLite HPR550 OH is published at a minimum of 1.1 equivalents per litre in the hydroxide form. Comparing the two numbers directly is meaningless; comparing them against the stated form is essential when a specification is being read across from a legacy datasheet.

Handling, conversion and rinse-up

A hydroxide form product is delivered ready for polishing duty, but it is also the form most sensitive to carbon dioxide pickup from air and to temperature. A chloride form product is more stable in storage and transport and is converted on site with caustic; the conversion step, the rinse volume and the caustic quality then become part of your commissioning procedure. Where the plant has reliable caustic handling and regeneration practice, the chloride form is often preferred for its robustness; where the resin goes straight into a polisher that is not regenerated in place, the hydroxide form removes a variable.

Shipping and storage considerations

Hydroxide form material should be kept within its published temperature range and protected from drying and from carbon dioxide. Whichever form is ordered, the delivery should be accompanied by the batch certificate stating the form, the exchange capacity, the moisture content and the particle size distribution actually measured on that batch, not only the specification range.

Grades Considered for Condensate Polishing Duty

AmberLite HPR550 OH

A gel, uniform particle size, Type I strong base anion resin supplied in the hydroxide form. Published total exchange capacity is a minimum of 1.1 equivalents per litre, moisture content 55.0 to 65.0 per cent, particle size 590 plus or minus 50 micrometres, uniformity coefficient 1.10 or below, particle density 1.08 grams per millilitre and loading density 660 grams per litre. Whole beads are a minimum of 95 per cent, average crush strength a minimum of 350 grams per bead, and expansion on conversion from chloride to hydroxide is below 25 per cent. Ionic conversion is stated as hydroxide 95 per cent or more, carbonate 5 per cent or less and chloride 0.5 per cent or less, with extractable metals reported on a dry basis. The maximum operating temperature is 100 degrees Celsius. This grade was previously marketed as DOWEX MONOSPHERE 550A(OH).

AmberLite HPR550 Cl

The chloride form of the same gel, uniform particle size family. Published total exchange capacity is a minimum of 1.35 equivalents per litre in the chloride form, moisture content 42.0 to 49.0 per cent, particle size 550 plus or minus 50 micrometres, uniformity coefficient 1.1 or below, particle density 1.09 grams per millilitre and loading density 690 grams per litre. Whole beads are a minimum of 95 per cent and average crush strength a minimum of 350 grams per bead. The chloride form is the more stable option for storage and for plants that regenerate in place. The former designation was DOWEX MONOSPHERE 550A.

AmberLite HPR9000 OH

A macroporous Type I strong base anion resin with a trimethylammonium functional group, supplied in the hydroxide form. Published total exchange capacity is a minimum of 0.80 equivalents per litre, moisture content 66.0 to 75.0 per cent, particle size 650 plus or minus 50 micrometres, uniformity coefficient 1.2 or below, particle density 1.05 grams per millilitre and loading density 660 grams per litre. Whole beads are a minimum of 95 per cent; ionic conversion is hydroxide 95 per cent or more, carbonate 5.0 per cent or less and chloride 0.20 per cent or less, with extractable metals reported on a dry basis. Expansion on conversion from chloride to hydroxide is 25 per cent or less, and the maximum operating temperature is 100 degrees Celsius. The open pore structure is intended for duty where surface fouling and physical, osmotic and oxidative stress limit the life of a gel resin. The former designation was AMBERJET 9000 OH.

AmberLite HPR900 SO4

A macroporous strong base anion resin supplied in the sulfate form, published at a minimum of 1.0 equivalent per litre on the chloride basis, moisture content 60.0 to 68.0 per cent, particle size 500 to 700 micrometres, uniformity coefficient 1.45 or below, particle density 1.09 grams per millilitre and loading density 695 grams per litre. Whole beads are a minimum of 95 per cent and the grade is characterised by a strong osmotic crush test result of 92 per cent or more, which is the reason it is specified where repeated turnover and osmotic shock dominate. Expansion is 15 per cent or less from sulfate to hydroxide and 25 per cent or less from chloride to hydroxide. The former designation was AmberSep 900 SO4.

AmberLite HPR4800 OH

A gel Type I strong base anion resin in the hydroxide form, published at a minimum of 1.0 equivalent per litre, moisture content 58.0 to 74.0 per cent, particle size 610 plus or minus 50 micrometres, uniformity coefficient 1.1 or below, particle density 1.07 grams per millilitre and loading density 640 grams per litre. Ionic conversion is hydroxide 95 per cent or more and carbonate 5 per cent or less; expansion from chloride to hydroxide is 20 per cent. Its published temperature limit is 60 degrees Celsius in the hydroxide form and 100 degrees Celsius in the chloride form, which is the single most important boundary to check before specifying it into a hot condensate duty. The former designation was DOWEX MARATHON A OH.

Published specification comparison

Grade

Matrix

Ionic form

Total exchange capacity

Moisture

Particle size

Uniformity coefficient

Loading density

Maximum temperature

AmberLite HPR550 OH

Gel, uniform

OH

>= 1.1 eq/L

55.0-65.0%

590 +/- 50 um

<= 1.10

660 g/L

100 C

AmberLite HPR550 Cl

Gel, uniform

Cl

>= 1.35 eq/L

42.0-49.0%

550 +/- 50 um

<= 1.1

690 g/L

100 C

AmberLite HPR9000 OH

Macroporous, Type I

OH

>= 0.80 eq/L

66.0-75.0%

650 +/- 50 um

<= 1.2

660 g/L

100 C

AmberLite HPR900 SO4

Macroporous

SO4

>= 1.0 eq/L (Cl basis)

60.0-68.0%

500-700 um

<= 1.45

695 g/L

100 C

AmberLite HPR4800 OH

Gel, Type I

OH

>= 1.0 eq/L

58.0-74.0%

610 +/- 50 um

<= 1.1

640 g/L

60 C (OH) / 100 C (Cl)

AmberLite HPR4200 Cl

Gel, Type I

Cl

>= 1.30 eq/L

49.0-55.0%

650 +/- 50 um

<= 1.25

670 g/L

60 C (OH) / 100 C (Cl)

AmberLite IRA402 Cl

Gel

Cl

>= 1.20 eq/L

49.0-59.0%

600-750 um

<= 1.80

670 g/L

60 C (OH) / 100 C (Cl)

 

Pairing the Anion Resin with the Cation Component

Density and particle size matching

In a mixed bed the two components must separate on backwash, and separation is governed by the difference in wet density and by the particle size distributions. AmberLite HPR550 OH has a particle density of 1.08 grams per millilitre and AmberLite HPR9000 OH 1.05 grams per millilitre, while the strong acid cation resins in the same service are considerably denser: AmberLite HPR650 H is published at 1.22 grams per millilitre. That density difference, combined with matched uniform particle sizes, is what produces a clean interface.

Colour contrast for visual confirmation

Condensate polisher operators confirm layering visually after backwash. The cation component in these grades is a dark amber, while the anion component is a pale to clear amber, which is why the pairings below are recommended as sets rather than as individual grades. Specifying an anion resin of a different colour family can make an otherwise correct separation impossible to confirm.

Recommended cation partners

AmberLite HPR650 H

A gel, uniform particle size strong acid cation resin in the hydrogen form, published at a minimum of 2.0 equivalents per litre, moisture content 46.0 to 52.0 per cent, particle size 650 plus or minus 50 micrometres, uniformity coefficient 1.10 or below, particle density 1.22 grams per millilitre and loading density 785 grams per litre. Whole beads are a minimum of 95 per cent, average crush strength a minimum of 500 grams per bead, expansion from sodium to hydrogen form is 7 per cent, and the maximum operating temperature is 150 degrees Celsius. It is the cation partner most commonly associated with the HPR550 and HPR9000 anion grades in condensate polishing service.

AmberLite HPR1300 H

A gel, uniform particle size strong acid cation resin in the hydrogen form, published at a minimum of 2.0 equivalents per litre, moisture content 46.0 to 52.0 per cent, particle size 650 plus or minus 50 micrometres, uniformity coefficient 1.10 or below and loading density 785 grams per litre. Whole beads are a minimum of 95 per cent, average crush strength a minimum of 350 grams per bead and the maximum operating temperature is 120 degrees Celsius.

Pairing matrix

Service

Anion component

Cation component

Basis

Condensate polishing mixed bed, clean condensate

AmberLite HPR550 OH

AmberLite HPR650 H

Gel, uniform particle size pair with matched density difference and colour contrast

Condensate polishing mixed bed, fouling or stress limited

AmberLite HPR9000 OH

AmberLite HPR650 H

Macroporous anion resin for oxidative and osmotic stress

Layered or three-layer bed, high silica or fouling duty

AmberLite HPR900 SO4

AmberLite HPR1300 H

Macroporous anion grade with high osmotic crush resistance

Industrial demineralisation polishing

AmberLite HPR4200 Cl or IRA402 Cl

AmberLite HPR1200 H or HPR1300 H

Type I gel anion resins for single or stratified anion duty

Service and laboratory polishing

AmberLite MB20 H/OH

Supplied pre-mixed

Ready-to-use mixed bed, loading density 710 g/L

 

Bed Configurations and the Role of Inert Resins

Layered and stratified beds

In a layered bed the resins are held in distinct zones by density and particle size. The anion resin sits above the cation resin, and the interface quality determines both the run length and the regenerant efficiency. Uniform particle size grades with a uniformity coefficient of 1.10 or below are the practical requirement here; a broad distribution will not hold a sharp boundary through repeated cycles.

Three-layer configurations

Where the condensate carries oil, corrosion products or organic material, a three-layer arrangement places a heavy inert medium at the bottom, the cation resin in the middle and the anion resin on top, so that the active resins are protected and the solids are taken up in the inert zone. Macroporous anion grades are the usual choice for the anion layer in this arrangement because of their tolerance of fouling and osmotic shock.

Inert upper-layer resins

AmberLite 14i is a polypropylene inert medium with a particle size of 1.2 to 1.5 millimetres, a particle density of 0.95 grams per millilitre and a loading density of 500 to 580 grams per litre, used as a floating upper layer in co-current and stratified beds. AmberLite 62i is a polyethylene inert medium with a particle size of 2.5 to 4.0 millimetres, a particle density of 0.95 grams per millilitre and a loading density of 620 grams per litre, used as the upper layer in backwash-filled beds. Because both are less dense than water they remain on top of the charge, keep the active resins in place during flow surges and distribute the incoming condensate evenly.

Pre-mixed and non-separable mixed beds

AmberLite MB20 H/OH is supplied as a ready-to-use mixture of strong acid cation resin in the hydrogen form and Type I strong base anion resin in the hydroxide form, with the cation component at 38 to 44 per cent and the anion component at 56 to 62 per cent by volume, a loading density of 710 grams per litre and a maximum operating temperature of 60 degrees Celsius. It is intended for service demineralisation and polishing duties where no regeneration facility exists. AmberTec MR-450 UPW H/OH is a non-separable mixed bed for final ultrapure water polishing, with the cation component published at a minimum of 2.0 equivalents per litre and the anion component at a minimum of 1.1 equivalents per litre, both at a uniformity coefficient of 1.1 or below, a loading density of 704 grams per litre and a narrow operating window of 15 to 25 degrees Celsius; it is not regenerated and is replaced as a complete charge. Neither of these products should be specified into a regenerative condensate polisher.

Operating Envelope and Applicability Boundaries

Temperature limits by grade and form

The published maximum temperature is not a single number per product. AmberLite HPR4800, AmberLite HPR4200 and AmberLite IRA402 are each limited to 60 degrees Celsius in the hydroxide form and 100 degrees Celsius in the chloride form. AmberLite HPR550, HPR9000 and HPR900 are published at a maximum of 100 degrees Celsius. AmberLite MB20 H/OH is limited to 60 degrees Celsius and AmberTec MR-450 UPW to a 15 to 25 degrees Celsius window. Where condensate temperature approaches the published ceiling, the grade should be selected on the chloride form limit only if the resin will actually be operated in that form.

Oxidative stress

Dissolved oxygen in condensate, combined with elevated temperature and the presence of amines, is the principal route to functional group loss in any strong base anion resin. Macroporous grades are specified where this stress is unavoidable, but no strong base anion resin should be exposed to oxidising agents such as nitrating compounds used for iron removal without the manufacturer's written confirmation.

Osmotic shock

The largest osmotic stress occurs at regeneration, when the bead moves between a concentrated regenerant and a dilute rinse, and again at commissioning if a dry or partially dried bead is contacted with water. Gel resins are the more sensitive; the sulfate form of AmberLite HPR900 is published with a strong osmotic crush result precisely because it is specified for duties where this stress is repeated.

Where these grades should not be used

Do not specify a hydroxide form gel anion resin into a duty where the bed may dry out, where the condensate carries significant organic loading without a protective weak base or inert layer, or where the temperature exceeds the published limit for the form actually supplied. Do not specify a non-separable mixed bed into a regenerative polisher, and do not mix anion grades of different colour families into a bed that must be confirmed by visual layering.

Acceptance Criteria Before the Resin Is Loaded

Documentation to request with the shipment

Ask for the batch certificate showing total exchange capacity and the form it is stated on, moisture content, particle size distribution including the uniformity coefficient, whole bead percentage, and the extractable metal results. Ask also for the handling and commissioning procedure for the specific ionic form supplied.

Incoming inspection

Check bead appearance and freedom from fines, verify the wet state of the sample, and confirm the reported density against the value used in the bed design. Where a mixed bed is being charged from two separate bags, confirm that both certificates are for the same recommended pairing rather than for two grades that happen to share a particle size.

Commissioning and rinse-up targets

Wet the resin according to the form supplied, avoid air entrapment, and establish a baseline conductivity and silica result at design flow before the bed is placed in continuous service. Record the rinse volume required to reach that baseline; it is the most useful early indicator of whether the charge was handled correctly.

Applications

Condensate polishing in thermal and combined-cycle plant

The grades above are specified for condensate polishing service where the objective is low ionic leakage and a predictable run length between backwashes, with the anion component chosen for the fouling and oxidative environment actually present.

Power and desalination duty

In plants where condensate polishing and desalination duties share a water chemistry organisation, the same Type I strong base anion grades serve final polishing after reverse osmosis and electrodeionation, with the choice between gel and macroporous structure driven by the organic and particulate load of the feed.

Industrial demineralisation polishers

Where the duty is bulk demineralisation rather than condensate polishing, chloride form Type I gel resins such as AmberLite HPR4200 Cl and IRA402 Cl are the usual specification, with IRA402 Cl indicated where low silica leakage from a high-silica feed is the controlling requirement.

Supply and Enquiry

Send the grade or legacy designation, the ionic form, the volume in litres, the vessel data and the condensate analysis, and we will confirm availability, the corresponding product data sheet and a written selection review. Batch documentation, packaging options and delivery terms are confirmed at enquiry stage against the grade and origin actually supplied.

Related FG Water Resources

•  Ion Exchange and Adsorption Resin: https://www.fgwater.com/Ion-Exchange-and-Adsorption-Resin/

•  International Brand Resins: https://www.fgwater.com/International-Brand-Resins/

•  Strong Base Anion Exchange Resin (SBA): https://www.fgwater.com/China-Make-Resins/169.html

•  Mixed Bed IX Resin: https://www.fgwater.com/China-Make-Resins/166.html

•  AmberLite HPR550 OH: https://www.fgwater.com/International-Brand-Resins/667.html

•  AmberLite HPR650 H: https://www.fgwater.com/International-Brand-Resins/666.html

•  AmberLite HPR650 H for condensate polishing: https://www.fgwater.com/International-Brand-Resins/668.html

•  AmberLite HPR4200 Cl: https://www.fgwater.com/International-Brand-Resins/672.html

•  AmberLite IRA402 Cl: https://www.fgwater.com/International-Brand-Resins/675.html

•  AmberLite IRN160 H/OH: https://www.fgwater.com/International-Brand-Resins/683.html

•  AmberTec MR-450 UPW H/OH: https://www.fgwater.com/International-Brand-Resins/685.html

•  AmberTec UP6040 OH: https://www.fgwater.com/International-Brand-Resins/687.html

•  AmberLite MB20 H/OH: https://www.fgwater.com/International-Brand-Resins/692.html

•  Power Plant Pure Water: https://www.fgwater.com/Power-Plant-Pure-Water/137.html

•  Boiler Feed Water: https://www.fgwater.com/Boiler-Feed-Water/123.html

•  Electrodeionization EDI Stack Module: https://www.fgwater.com/Electrodeionization-EDI-Stack-Module/

•  Product Literature: https://www.fgwater.com/Product-Literature/

Frequently Asked Questions

Should we order the chloride form or the hydroxide form for a condensate polisher?

Order the hydroxide form where the resin goes directly into a polisher that is not regenerated in place, because it removes the on-site conversion step and its variability. Order the chloride form where the plant regenerates in place and has controlled caustic handling, because it is the more stable form for storage and transport. Note that the published capacity figures differ between the two forms, so specifications must always be read with the form stated.

Can a macroporous strong base anion resin replace a gel grade in an existing mixed bed?

Yes, and it is the normal response where run length is limited by fouling, corrosion products or repeated turnover rather than by capacity. Expect a lower total exchange capacity per litre in exchange for the better foulant and osmotic tolerance, and confirm that the particle density and particle size still give a clean separation from the existing cation component.

How do we confirm that the anion and cation resins will separate properly?

Compare the published particle densities and uniformity coefficients of the two grades, and confirm that the pair is offered as a recommended combination. In service, separation is confirmed visually after backwash: the cation component in these grades is dark amber and the anion component is pale to clear, which is what makes the boundary visible.

What temperature limit applies once the resin is in the hydroxide form?

Use the published limit for the form in which the resin is actually operated. Several Type I gel grades are limited to 60 degrees Celsius in the hydroxide form and 100 degrees Celsius in the chloride form, while the HPR550, HPR9000 and HPR900 grades are published at 100 degrees Celsius. A condensate temperature that is acceptable for a chloride form charge may already exceed the hydroxide form limit.

Why does silica leakage rise before the resin is exhausted?

Silica is held weakly, and its breakthrough is more sensitive to loss of strong base sites, to regeneration efficiency and to flow distribution than to total capacity. A silica rise with otherwise normal conductivity usually indicates a regeneration or distribution issue, or functional group loss from oxidative and thermal stress, rather than simple capacity exhaustion.

Is a Type II strong base anion resin acceptable for condensate polishing?

It is not the recommended choice. Type II chemistry releases more silica and is more limited thermally, particularly in the hydroxide form. For condensate and final polishing duty, Type I materials are the specification, and the choice within Type I is between a gel and a macroporous matrix.

How is the resin charge for our polisher determined?

The charge follows the vessel geometry: the bed depth and the freeboard required for backwash expansion set the volume, and the loading density published for each grade converts that volume into the delivered quantity. Send the vessel drawing and the condensate analysis and the charge can be calculated for the specific grade and form.

What documentation should accompany the delivery?

A batch certificate reporting the measured total exchange capacity and its ionic form, moisture content, particle size distribution with the uniformity coefficient, whole bead percentage, crush strength where published, and extractable metals, together with the commissioning procedure for the form supplied.

Request a Condensate Polishing Selection Review

Send the current bed arrangement, the condensate and steam chemistry, the operating temperature and the run length you are trying to achieve, and our water chemistry team will return a written grade recommendation with the corresponding product data sheets and a quotation for the volume you need.

Email [email protected] or contact us on WhatsApp +86-13646187144. Wuxi Fenigal Science and Technology Co., Ltd., Building 9, Industrial Design Park, Dicui Rd. 100, Binhu, Wuxi, Jiangsu, China. Online enquiry: https://www.fgwater.com/Contact-Us/


Project Inquiry · Technical & Commercial

Send Your Water Treatment Requirement

Tell us the feedwater, required capacity, target water quality and project conditions. Your inquiry email will automatically include the page you are viewing so our team can understand the exact product, technology or reference that led to your request.

  • Feedwater source / available analysis
  • Design flow or required production capacity
  • Target product-water quality or process duty
  • Project country, operating conditions and delivery target
Inquiry context Current page details will be attached automatically.